HOME > Products > Cabling/Networking
Beckhoff

EL1008

Cabling and Networking

Codice prodotto: EL1008

Richiedi preventivo

EL1008 | Cabling and Networking | Beckhoff

EL1008 is a Beckhoff EtherCAT terminal designed for the acquisition of 8 digital inputs at 24 V DC in industrial automation systems. The module detects binary signals from the field level and transmits them, in an electrically isolated form, to the higher-level automation unit, supporting reliable signal management within the control cabinet.

Each channel features status indication via LED, facilitating diagnostics and control activities during installation, maintenance, and commissioning. The integrated 3 ms input filter helps reduce the effects of mechanical contact bounce, improving the stability of digital signal readings.

The 1-wire connection technology, compact format, and IP20 protection rating allow for integration into automation cabinets. With an operating temperature of -25…+60 °C, electrical isolation up to 500 V, and CE, UL, ATEX, IECEx, DNV, and cFMus compliance, the terminal represents a reliable solution for standard industrial applications and environments with specific requirements.

Discover our range of Cabling/Networking!

... leggi tutto

Caratteristiche principali

Connection technology
1-wire
Specification
EN 61131-2, type 1/3
Number of inputs
8
Nominal voltage
24 V DC (-15%/+20%)
“0” signal voltage
-3…+5 V (EN 61131-2, type 3)
“1” signal voltage
11…30 V (EN 61131-2, type 3)
Input current
typ. 3 mA (EN 61131-2, type 3)
Input filter
typ. 3 ms
Distributed clocks
–
Current consumption power contacts
typ. 2 mA + load
Current consumption E-bus
typ. 90 mA
Electrical isolation
500 V (E-bus/field potential)
Configuration
no address or configuration setting
Special features
standard input terminal for bouncing signals (filter 3 ms)
Weight
approx. 55 g
Operating temperature
-25…+60°C
Storage temperature
-40…+85°C
Relative humidity
95%, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4

Richiedi preventivo